The Safe torque off function
Contents of this chapter
This chapter describes the Safe torque off (STO) function of the drive and gives instructions
for its use.
Description
WARNING!
In case of parallel-connected drives or dual-winding motors, the STO must be
activated on each drive to remove the torque from the motor.
The Safe torque off function can be used, for example, as the final actuator device of safety
circuits that stop the drive in case of danger (such as an emergency stop circuit). Another
typical application is a prevention of unexpected start-up function that enables short-time
maintenance operations like cleaning or work on non-electrical parts of the machinery without
switching off the power supply to the drive.
When activated, the Safe torque off function disables the control voltage of the power
semiconductors of the drive output stage (A, see the diagrams below), thus preventing the
drive from generating the torque required to rotate the motor. If the motor is running when
Safe torque off is activated, it coasts to a stop.
The Safe torque off function has a redundant architecture, that is, both channels must be
used in the safety function implementation. The safety data given in this manual is calculated
for redundant use, and does not apply if both channels are not used.
The Safe torque off function complies with these standards:
Name
Standard
Safety of machinery – Electrical equipment of machines – Part 1: General
requirements
IEC 60204-1:2016
EN 60204-1:2018
15
The Safe torque off function 201
Содержание ACS880-07LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 07LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...16 Resistor braking Further information 12 Table of contents ...
Страница 22: ...22 ...
Страница 63: ...Mechanical installation 63 10 ...
Страница 64: ...64 ...
Страница 91: ...a b c 4 a 8 b 16 18 PE PE 10 13 12 Electrical installation 91 11 ...
Страница 97: ...11 Reinstall the shrouding removed earlier 12 Close the cubicle door Electrical installation 97 11 ...
Страница 100: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 100 Electrical installation ...
Страница 104: ...104 ...
Страница 118: ...118 ...
Страница 124: ...124 ...
Страница 138: ...8 9 138 Maintenance ...
Страница 139: ...11 12 12 6 10 Maintenance 139 ...
Страница 150: ...150 ...
Страница 160: ...160 ...
Страница 183: ...Technical data 183 ...
Страница 184: ...184 Technical data ...
Страница 189: ... Dimension drawing examples ACS880 07LC 0850A 7 Dimensions 189 ...
Страница 190: ...ACS880 07LC 1660A 7 6 pulse 190 Dimensions ...
Страница 191: ...ACS880 07LC 1660A 7 A004 12 pulse Dimensions 191 ...
Страница 192: ...ACS880 07LC 3260A 7 192 Dimensions ...
Страница 193: ...Cabinet height and depth Marine construction option C121 IP42 side view Non marine IP42 side view Dimensions 193 ...
Страница 194: ...Location and size of input terminals 600 mm with main breaker single busbar bottom cable entry 194 Dimensions ...
Страница 195: ... 600 mm with main breaker double busbar bottom cable entry Dimensions 195 ...
Страница 197: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 197 ...
Страница 198: ...Inverter module cubicle with three R8i modules bottom cable exit 198 Dimensions ...
Страница 199: ...Brake chopper cubicle Dimensions 199 ...
Страница 200: ...200 ...
Страница 216: ... Declaration of conformity 216 The Safe torque off function ...
Страница 217: ...The Safe torque off function 217 ...
Страница 218: ...218 ...
Страница 220: ...220 ...