1.
Stop the drive and do the steps in section
Electrical safety precautions (page 15)
before
you start the work.
2.
Make sure that the resistor cable is connected to the resistor and disconnected from
the drive output terminals.
3.
At the drive end, connect the R+ and R- conductors of the resistor cable together.
Measure the insulation resistance between the conductors and the PE conductor with
a measuring voltage of 1000 V DC. The insulation resistance must be more than 1 Mohm.
R-
R+
ohm
PE
1 kV DC,
> 1 Mohm
Compatibility with IT (ungrounded), corner-grounded delta,
midpoint-grounded delta and TT systems
The standard drive with no EMC filter connected can be installed to a symmetrically grounded
TN-S system. If you install the drive to another system, you may need to disconnect the
EMC filter and ground-to-phase varistors. See
ACS880 frames R1 to R11 EMC filter and
ground-to-phase varistor disconnecting instructions
(3AUA0000125152 [English]).
WARNING!
Do not install the drive with EMC filter E200 to a system that the filter is
not suitable for. This can cause danger, or damage the drive.
WARNING!
Do not install the drive with ground-to-phase varistor connected to a system that
the varistor is not suitable for. If you do, the varistor circuit can be damaged.
Grounding the drive module
Ground the drive module from its top back grounding hole to the cabinet frame or from the
module PE terminal to the cabinet PE busbar.
Electrical installation 85
11
Содержание ACS880-04FXT
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 40: ...40 ...
Страница 54: ...54 ...
Страница 82: ...82 ...
Страница 86: ...M10 86 Electrical installation ...
Страница 106: ...106 ...
Страница 114: ...FSO xx safety functions module connection X12 See the user manual of the FSO xx module 114 Control unit of the drive ...
Страница 118: ...118 ...
Страница 122: ...122 ...
Страница 132: ...132 ...
Страница 136: ...136 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with optional full size input and output power cable terminals and IP20 shrouds 162 Dimension drawings ...
Страница 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Страница 164: ...3AXD50000038119 164 Dimension drawings ...
Страница 182: ... Declaration of conformity 182 The Safe torque off function ...
Страница 183: ...The Safe torque off function 183 ...
Страница 184: ...184 ...