Notes:
1)
See section
.
2)
See chapter
The Safe torque off function (page 167)
.
3)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use. 1 =
Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
4)
Constant speed 1 is defined by parameter 22.26.
5)
See section
6)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for digital
inputs floats; in practice, selects whether the digital inputs are used in current sinking or
sourcing mode). See the ground isolation diagram in
BCU-02/12/22 control units hardware
manual
(3AUA0000113605 [English]).
DICOM=DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
8)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input
selected by switch AI1. Change of setting requires reboot of control unit.
9)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input
selected by switch AI2. Change of setting requires reboot of control unit.
External power supply for the control unit (XPOW)
The control unit is powered from a 24 V DC, 2 A supply through terminal block XPOW. With
a type BCU control unit, a second supply can be connected to the same terminal block for
redundancy.
Using an external supply is recommended if
•
the control unit needs to be kept operational during input power breaks, for example,
because of continuous fieldbus communication
•
immediate restart is needed after a power break (that is, no control unit power-up delay
is allowed).
DI6 as a PTC sensor input
A PTC sensor can be connected to this input for motor temperature measurement as follows.
The sensor can alternatively be connected to FEN-xx encoder interface module. At the
sensor end of the cable, leave the shields unconnected or ground them indirectly via a
high-frequency capacitor with a few nanofarads, for example 3.3 nF / 630 V. The shield can
also be grounded directly at both ends if they are in the same ground line with no significant
voltage drop between the end points. See the firmware manual of the inverter unit for
parameter settings.
Control unit of the drive 111
Содержание ACS880-04FXT
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 40: ...40 ...
Страница 54: ...54 ...
Страница 82: ...82 ...
Страница 86: ...M10 86 Electrical installation ...
Страница 106: ...106 ...
Страница 114: ...FSO xx safety functions module connection X12 See the user manual of the FSO xx module 114 Control unit of the drive ...
Страница 118: ...118 ...
Страница 122: ...122 ...
Страница 132: ...132 ...
Страница 136: ...136 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with optional full size input and output power cable terminals and IP20 shrouds 162 Dimension drawings ...
Страница 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Страница 164: ...3AXD50000038119 164 Dimension drawings ...
Страница 182: ... Declaration of conformity 182 The Safe torque off function ...
Страница 183: ...The Safe torque off function 183 ...
Страница 184: ...184 ...