Guidelines for planning the electrical installation 67
Separate control cable ducts
Lead 24 V and 230 V (120 V) control cables in separate ducts unless the 24 V cable is
insulated for 230 V (120 V) or insulated with an insulation sleeving for 230 V (120 V).
Continuous motor cable shield or enclosure for equipment in the
motor cable
To minimize the emission level when safety switches, contactors, connection boxes or
similar equipment are installed on the motor cable between the drive and the motor:
•
European Union: Install the equipment in a metal enclosure with 360 degree
grounding for the shields of both the incoming and outgoing cable, or connect the
shields of the cables otherwise together.
•
US: Install the equipment in a metal enclosure in a way that the conduit or motor cable
shielding runs consistently without breaks from the drive to the motor.
Implementing thermal overload and short-circuit
protection
Protecting the drive and input power cable in short-circuits
Protect the drive with fuses (a) and the input cable with fuses (b) or a circuit breaker as
shown below:
Size the fuses or the circuit breaker at the distribution board according to local regulations
for the input cable protection. Select the fuses for the drive according to the instructions
given in chapter
The fuses for the drive protection will restrict drive
damage and prevent damage to adjoining equipment in case of a short-circuit inside the
drive.
24 V
24 V
230 V
(120 V)
230 V
(120 V)
~
~
M
3~
a
b
ACS880-04F
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...