Guidelines for planning the electrical installation 63
Typical power cable sizes
The table below gives copper and aluminum cable types with concentric copper shield for
the drives with nominal current. See also
Terminal and lead-through data for the power
on page
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C
(158 °F) (EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local
safety regulations, appropriate input voltage and the load current of the drive
.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Alternative power cable types
The recommended and not allowed power cable types to be used with the drive are
presented below.
Recommended power cable types
Drive type
ACS880-
04-
IEC
1)
US
2)
Cu cable
type
Al cable
type
Cu cable type
Al cable type
mm
2
mm
2
AWG/kcmil
AWG/kcmil
U
N
= 400 V
725A-3
3 × (3×185)
4 × (3×185)
3×500 MCM or 4×300 MCM
3×500 MCM or 4×300 MCM
820A-3
3 × (3×240)
4 × (3×240)
3×600 MCM or 4×400 MCM
3×700 MCM or 4×500 MCM
880A-3
3 × (3×240)
4 × (3×240)
3×600 MCM or 4×400 MCM
4×500 MCM
U
N
= 500 V
715A-5
3 × (3×185)
4 × (3×185)
3×500 MCM or 4×300 MCM
3×600 MCM or 4×400 MCM
820A-5
3 × (3×240)
4 × (3×240)
3×600 MCM or 4×400 MCM
4×500 MCM
880A-5
3 × (3×240)
4 × (3×240)
3×600 MCM or 4×400 MCM
4×500 MCM
3AXD00000588487
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. The shield must agree with the requirements of
IEC 61800-5-1, see page
. Check with local / state / country electrical codes
for allowance.
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. A separate PE conductor is required if the shield does not
agree with the requirements of IEC 61800-5-1, see page
Symmetrical shielded cable with three phase conductors and symmetrically
constructed PE conductor, and a shield. The PE conductor must agree with the
requirements of IEC 61800-5-1, see page
PE
PE
PE
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...