Ambient conditions

Safe torque off (STO)

The drive has a Safe torque off function (STO) in accordance with IEC/EN 61800-5-2. It can be used, for example, as the final 

actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit).
When activated, the STO function disables the control voltage of the power semiconductors of the drive output stage, thus 

preventing the drive from generating the torque required to rotate the motor. The control program generates an indication 

as defined by parameter 

31.22

. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the 

activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation. 

The safety data given in this manual is calculated for redundant use, and does not apply if both channels are not used.

WARNING! 

The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.

Notes:

If stopping by coasting is not acceptable, stop the drive and machinery using the appropriate stop mode before 

activating the STO.

The STO function overrides all other functions of the drive.

Wiring

The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the 

switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.

Validation

To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent 

person with adequate expertise and knowledge of the safety function. The test procedures and report must be 

documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware 

manual.

Technical data

Minimum voltage at IN1 and IN2 to be interpreted as “1”: 17 V DC

STO reaction time (shortest detectable break): 1 ms

STO response time: 2 ms (typical), 5 ms (maximum)

Fault detection time: Channels in different states for longer than 200ms

Fault reaction time: Fault detection time + 10ms

STO fault indication (parameter 

31.22

) delay: < 500 ms

STO warning indication (parameter 

31.22

) delay: < 1000 ms

Safety integrity level (EN 62061): SIL 3

Performance level (EN ISO 13849-1): PL e

The drive STO is a type A safety component as defined in IEC 61508-2.
For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual

Markings

The applicable markings are shown on the type designation label of the drive.

Related documents

Installation altitude

0 … 4000 m (0 … 13123 ft) above sea level. The output current must be derated at 

altitudes above 1000 m (3281 ft). The derating is 1% for each 100 m (328 ft) above 

1000 m (3281 ft). 
TN (grounded) and IT (ungrounded) systems.Installing on 525…690 V corner-grounded 

or midpoint-grounded delta systems is not allowed.

Surrounding air temperature

Operation: -15 … +55 °C (5 … 131 °F). Frost is not permitted. The rated output current 
must be derated by 1% for each 1 °C (1.8 °F) over 40 °C (104 °F) for IP21 (UL Type 1) drives 
and for IP55 (UL Type 12) frames R1…R7 (for frames R8 and R9, see the hardware 
manual). Storage (in the package): -40 to +70 °C (-40 to +158 °F).

CE

UL 

RCM  EAC EIP 

green WEEE TÜV 

Nord CSA

UKCA

Document

Code (English)

ACS880-01 hardware manual

3AXD50000078093

ACS880 primary control program firmware manual

3AXD50000085967

ACx-AP-x assistant control panels user’s manual

3AUA0000085685

Drive composer PC tool user's manual

3AUA0000094606

Converter module capacitor reforming instructions

3BFE64059629

Содержание ACS880-01 Series

Страница 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Страница 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Страница 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Страница 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Страница 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Страница 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Страница 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Страница 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Страница 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Страница 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Страница 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Страница 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Страница 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Страница 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Страница 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Страница 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Отзывы: