![ABB ACS880-01 Series Скачать руководство пользователя страница 63](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621063.webp)
Program features 63
Adaptive programming
Conventionally, the user can control the operation of the drive by parameters.
However, the standard parameters have a fixed set of choices or a setting range. To
further customize the operation of the drive, an adaptive program can be constructed
out of a set of function blocks.
The Drive composer pro PC tool (version 1.10 or later, available separately) has an
Adaptive programming feature with a graphical user interface for building the custom
program. The function blocks include the usual arithmetic and logical functions, as
well as eg. selection, comparison and timer blocks. The program can contain a
maximum of 20 blocks. The adaptive program is executed on a 10 ms time level.
For selecting input to the program, the user interface has pre-selections for the
physical inputs, common actual values, and other status information of the drive.
Parameter values as well as constants can also be defined as inputs. The output of
the program can be used eg. as a start signal, external event or reference, or
connected to the drive outputs. Note that connecting the output of the adaptive
program to a selection parameter will write-protect the parameter.
The status of the adaptive program is shown by parameter
. The adaptive program can be disabled by
.
For more information, see the
Adaptive programming application guide
(3AXD50000028574 [English]).
Application programming
The functions of the firmware program can be extended with application
programming. Application programmability is available as N8010.
Application programs can be built out of function blocks based on the IEC 61131-3
standard using a PC tool available separately.
For more information, see
Programming manual: Drive application programming
(IEC 61131-3)
(3AUA0000127808 [English]).
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...