![ABB ACS880-01 Series Скачать руководство пользователя страница 167](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621167.webp)
Parameters 167
Drive status word 1.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Enabled
1 = Both run enable (see par.
) and start enable (
) signals are
present, and Safe torque off has not been activated.
Notes:
• In I/O or local control, clearing this bit makes the drive enter the
SWITCH-ON INHIBITED state (see page
).
• This bit is not affected by the presence of a fault.
1
Inhibited
1 = Start inhibited. See parameters
and
for the source of the
inhibiting signal.
2
DC charged 1 = DC circuit has been charged. If present, the DC switch is closed, and
charging switch is open.
0 = Charging not complete. If the inverter unit is not equipped with a DC
switch (F286), check setting of
.
3
Ready to
start
1 = Drive is ready to receive a start command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being controlled)
7
Limiting
1 = Any operating limit (speed, torque, etc.) is active
8
Local control 1 = Drive is in local control
9
(see page
10
Ext1 active
1 = Control location EXT1 active
11
Ext2 active
1 = Control location EXT2 active
12
Reserved
13
Start request 1 = Start requested
14…15 Reserved
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...