![ABB ACS880-01 Series Скачать руководство пользователя страница 126](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621126.webp)
126 Program features
Miscellaneous
User parameter sets
The drive supports four user parameter sets that can be saved to the permanent
memory and recalled using drive parameters. It is also possible to use digital inputs to
switch between user parameter sets.
A user parameter set contains all editable values in parameter groups 10…99 except
• forced I/O values such as parameters
• I/O extension module settings (groups 14…16)
• fieldbus communication enable parameters (
and
)
• other fieldbus communication settings (groups 51…56 and 58)
• encoder configuration settings (groups 92…93), and
• parameter
As the motor settings are included in the user parameter sets, make sure the settings
correspond to the motor used in the application before recalling a user set. In an
application where different motors are used with the drive, the motor ID run needs to
be performed with each motor and the results saved to different user sets. The
appropriate set can then be recalled when the motor is switched.
Settings
Parameters
).
Parameter checksum calculation
A parameter checksum can be calculated from a user-definable set of parameters to
monitor changes in the drive configuration. The calculated checksum is compared to
1…4 reference checksums; in case of a mismatch, an event (a pure event, warning or
fault) is generated.
By default, the set of parameters included in the calculation contain most parameters
with the exception of
• actual signals
• parameter group
• parameters that are activated to validate new settings (such as
• parameters that are not saved to the flash memory (such as
)
• parameters that are internally calculated from others (such as
• dynamic parameters (eg. parameters that vary according to hardware), and
• application program parameters.
The default set can be edited using the Drive customizer PC tool.
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...