Program features 77
8. Reset all faults and start the drive/inverter unit. The maximum current is now
automatically limited according to the new inverter configuration. A mismatch
between the number of detected modules (
) and the value set in
generate a fault.
After all modules have been reinstalled, parameter
must be
reset to 0 to disable the reduced run function. In case the inverter is equipped with a
charging circuit, the charging monitoring must be reactivated for all modules.
Settings
Parameters
) and
).
du/dt filter support
With an external du/dt filter connected to the output of the drive, bit 13 of
must be switched on. The setting limits the output switching
frequency. With frame size R5i…R7i inverter modules, the setting also forces the
drive/inverter module fan to full speed. Note that the setting is not to be activated with
inverter modules with internal du/dt filters.
Settings
Parameter
).