354 Fault tracing
0008 Speed feedback configuration
has changed.
Use parameter
to validate any changes in the
settings.
0009 No encoders configured to
encoder module
Configure the encoder in group
A798
Encoder option comm
loss
Encoder feedback not used as
actual feedback, or measured
motor feedback lost (and
parameter
is set to
Check that the encoder is selected as
feedback source in parameter
or
Check that the encoder interface module
is properly seated in its slot.
Check that the encoder interface module
or slot connectors are not damaged. To
pinpoint the problem, try installing the
module into a different slot.
0001 Failed answer to encoder
configuration message.
Contact your local ABB representative.
0002 Failed answer to adapter
watchdog disable message.
Contact your local ABB representative.
0003 Failed answer to adapter
watchdog enable message.
Contact your local ABB representative.
0004 Failed answer to adapter
configuration message.
Contact your local ABB representative.
0005 Too many failed answers inline
to speed and position
messages.
Contact your local ABB representative.
0006 DDCS driver failed.
Contact your local ABB representative.
A79B
BC short circuit
Short circuit in brake chopper
IGBT
Replace brake chopper if external. Drives
with internal choppers will need to be
returned to ABB.
Ensure brake resistor is connected and
not damaged.
A79C
BC IGBT excess
temperature
Brake chopper IGBT
temperature has exceeded
internal warning limit.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
Check resistor overload protection
function settings (parameters
).
Check minimum allowed resistor value
for the chopper being used.
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
A7A1
Mechanical brake
closing failed
Programmable warning:
Status of mechanical brake
acknowledgement is not as
expected during brake close.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
.
Check that acknowledgement signal
matches actual status of brake.
Code
(hex)
Warning
Cause
What to do
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...