290 Parameters
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required. A value
other than 0 activates the reduced run function.
If the control program cannot detect the number of modules
specified by this parameter, a fault (
) is
generated.
See section
(page
0 = Reduced run disabled
1…12 = Number of modules available
Note:
This parameter cannot be changed while the drive is
running.
0
0…65535
Number of inverter modules available
-
(Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules have
been detected by the control program.
-
0000h…FFFFh
Inverter modules connected.
1 = 1
0000b…0111b
Hardware options configuration word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Module 1
1 = Module 1 has been detected.
1
Module 2
1 = Module 2 has been detected.
…
…
…
11
Module 12
1 = Module 12 has been detected.
12…15 Reserved
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...