Parameters 243
Defines the “at setpoint” limits for torque control of the drive.
When the absolute difference between reference (
) and actual torque (
) is smaller than
, the drive is
considered to be “at setpoint”. This is indicated by bit 8 of
.
10.0%
0.0 … 300.0%
Limit for “at setpoint” indication in torque control.
See par.
Defines the trigger level for “above limit” indication in speed
control. When actual speed exceeds the limit, bit 10 of
1500.00 rpm
0.00 … 6000.00
rpm
“Above limit” indication trigger level for speed control.
See par.
Defines the trigger level for “above limit” indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of
is set.
50.00 Hz
0.00 … 100.00 Hz
“Above limit” indication trigger level for frequency control.
See par.
Defines the trigger level for “above limit” indication in torque
control. When actual torque exceeds the limit, bit 10 of
300.0%
0.0 … 1600.0%
“Above limit” indication trigger level for torque control.
See par.
Defines the number of decimal places of torque-related
parameters.
1
0…2
Number of decimal places of torque parameters.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
(%)
0 %
(%)
(%)
(%)
Drive at setpoint
(
bit 8 = 1)
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...