402 Fieldbus control through the embedded fieldbus interface (EFB)
Exception codes
The table below shows the Modbus exception codes supported by the embedded
fieldbus interface.
2Bh / 0Eh
Encapsulated Interface
Transport
Supported subcodes:
• 0Eh Read Device Identification: Allows reading the
identification and other information.
Supported ID codes (access type):
• 00h: Request to get the basic device identification
(stream access)
• 04h: Request to get one specific identification
object (individual access)
Supported Object IDs:
• 00h: Vendor Name (“ABB”)
• 01h: Product Code (for example, “AINFX”)
• 02h: Major Minor Revision (combination of contents
of parameters
).
• 03h: Vendor URL (“www.abb.com”)
• 04h: Product name (for example, “ACS860”)
Code
Name
Description
01h
ILLEGAL FUNCTION
The function code received in the query is not an
allowable action for the server.
02h
ILLEGAL DATA
ADDRESS
The data address received in the query is not an
allowable address for the server.
03h
ILLEGAL DATA VALUE
The requested Quantity of Registers is larger than the
drive can handle.
Note:
This error does not mean that a value written to
a drive parameter is outside the valid range.
04h
SLAVE DEVICE
FAILURE
The value written to a drive parameter is outside the
valid range. See section
06h
SLAVE DEVICE BUSY
The server is engaged in processing a long-duration
program command.
Code
Function name
Description
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...