370 Fault tracing
6481
Task overload
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
6487
Stack overflow
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A1
Internal file load
File read error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A2
Internal record load
Internal record load error.
Contact your local ABB representative.
64A3
Application loading
Application file incompatible or
corrupted.
Check the auxiliary code. See actions for
each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
8007 The application contains the
wrong system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
8008 The application is empty.
In Automation Builder, give a “Clean”
command and reload the application.
8009 The application contains
invalid tasks.
In Automation Builder, check application
task configuration, give a “Clean all”
command, and reload the application.
800A The application contains an
unknown target (system)
library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
64A5
Licensing fault
Running the control program is
prevented either because a
restrictive license exists, or
because a required license is
missing.
Record the auxiliary codes of all active
licensing faults and contact your product
vendor for further instructions.
64A6
Adaptive program
Error running the adaptive
program.
Check the auxiliary code (format
XXXX YYYY). “XXXX” specifies the
number of the function block (
0000
=
generic error). “YYYY” indicates the
problem (see actions for each code
below).
000A Program corrupted or block
non-existent
Restore the template program or
download the program to the drive.
000C Required block input missing
Check the inputs of the block.
000E Program corrupted or block
non-existent
Restore the template program or
download the program to the drive.
0011 Program too large.
Remove blocks until the error stops.
0012 Program is empty.
Correct the program and download it to
the drive.
Code
(hex)
Fault
Cause
What to do
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...