Parameters 291
Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING!
After switching any bits in this word,
recheck the values of the affected parameters.
Note:
This parameter cannot be changed while the drive is
running.
-
0000h…FFFFh
Hardware options configuration word 1.
1 = 1
(Only visible with a BCU control unit)
Filters the list of drive/inverter types listed by parameter
.
Note:
This parameter cannot be changed while the drive is
running.
No filter
All types listed.
1
-7 (525-690V)
-7 (525…690 V) types listed.
4
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Supply frequency
60 Hz
0 = 50 Hz; 1 = 60 Hz. Affects parameters
,
40.15
,
40.37
,
41.15
,
41.37
,
.
1
Emergency stop
Cat 0
1 = Emergency stop, Category 0, without FSO module. Affects
.
2
Emergency stop
Cat 1
1 = Emergency stop, Category 1, without FSO module. Affects
.
4
Externally powered
control unit
1 = Control unit powered externally. Affects
.
(Only visible with
a ZCU control unit)
5
DC supply switch
1 = DC switch monitoring active. Affects
.
(Only
visible with a ZCU control unit)
6
DOL motor switch 1 = Motor fan control active. Affects
,
.
7
xSFC-01 fuse
switch controller
1 = xSFC charging controller used. Affects
(Only visible with a
BCU control unit)
8
Service switch or
PTC/Pt100 relay
1 = Service switch or PTC/Pt100 relay connected. Affects
,
.
9
Output contactor
1 = Output contactor present. Affects
,
.
10
Brake resistor, sine
filter, IP54 fan
1 = Status (eg. thermal) switches connected to DIIL input. Affects
.
12
Reserved
13
du/dt filter
activation
1 = Active: An external du/dt filter is connected to the drive output.
The setting will limit the output switching frequency. With inverter
module frame sizes R5i to R7i, the fan of the module will be forced to
full speed.
Note:
This bit is to be left at 0 if the drive/inverter module
is equipped with internal du/dt filtering (for example, frame R8i
inverter modules with E205).
*See section
(page
).
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...