Parameters 257
Refresh settings
Validates any changed EFB configuration settings. Reverts
automatically to
.
1
Silent mode
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
selection of this parameter.
2
Displays the status of the EFB communication.
This parameter is read-only.
-
0000h…FFFFh
EFB communication status.
1 = 1
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of received packets addressed to the drive.
1 = 1
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of transmitted packets.
1 = 1
Displays a count of valid packets addressed to any device on
the bus. During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of all received packets.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Autobauding
Reserved
4
Wiring error
1 = Errors detected (A/B wires possibly swapped)
5
Parity error
1 = Error detected: check parameters
6
Baud rate error
1 = Error detected: check parameters
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device) detected during last 5
seconds
9
Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10
Comm loss
1 = 0 packets addressed to the drive received within timeout
(
11
CW/Ref loss
1 = No control word or references received within timeout
(
12
Not active
Reserved
13
Protocol 1
Reserved
14
Protocol 2
Reserved
15
Internal error
Reserved
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...