170 Parameters
Defines the derivation time of the speed controller. Derivative
action boosts the controller output if the error value changes.
The longer the derivation time, the more the speed controller
output is boosted during the change. If the derivation time is
set to zero, the controller works as a PI controller, otherwise
as a PID controller. The derivation makes the control more
responsive for disturbances. For simple applications
(especially those without an encoder), derivative time is not
normally required and should be left at zero.
The figure below shows the speed controller output after an
error step when the error remains constant. The speed error
derivative must be filtered with a low pass filter to eliminate
external disturbances.
0.000 s
0.000 … 10.000 s
Derivation time for speed controller.
1000 = 1 s
Defines the derivation filter time constant. See parameter
.
8 ms
0…10000 ms
Derivation filter time constant.
1 = 1 ms
No.
Name/Value
Description
Def
/
FbEq16
K
p
× e
Gain = K
p
= 1
T
I
= Integration time > 0
T
D
= Derivation time > 0
T
s
= Sample time period = 500 µs
e = Error value change between two samples
K
p
×
T
D
×
e
T
s
Controller output
e = Error value
Error value
Time
T
I
K
p
× e
%
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...