Application macros 89
Default control connections for the Torque control macro
External power input
24 V DC, 1.6 A
XP
OW
+24VI
1
GND
2
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
XR
O1
NO
1
COM
2
NC
3
Relay output RO2 [Modulating]
250 V AC / 30 V DC
2 A
XR
O2
NO
4
COM
5
NC
6
Relay output RO3 [Fault (-1)]
250 V AC / 30 V DC
2 A
XR
O3
NO
7
COM
8
NC
9
+24 V DC*
XD
24
+24VD
1
Digital input ground
DIGND
2
+24 V DC*
+24VD
3
Digital input/output ground
DIOGND
4
DI/DIO grounding selection jumpers
Digital input DI1 [Stop/Start]
XD
I
DI1
1
Digital input DI2 [Direction]
DI2
2
Digital input DI3 [Speed/Torque control selection]
DI3
3
Digital input DI4 [Constant speed 1]
DI4
4
Digital input DI5 [Acc/Dec ramp 1/2 selection]
DI5
5
Digital input DI6 or thermistor input
DI6
6
Start interlock (0 = Stop)
DIIL
A
Digital input/output DIO1 [Output: Ready]
XD
IO
DIO1
1
Digital input/output DIO2 [Output: Running]
DIO2
2
Reference voltage (+)
XA
I
+VREF
1
Reference voltage (–)
-VREF
2
Ground
AGND
3
Analog input AI1 [EXT1 Reference (Speed ref1)]
(Current or voltage, selectable by jumper AI1)
AI1+
4
AI1-
5
Analog input AI2 [EXT2 Reference (Torq ref1]
(Current or voltage, selectable by jumper AI2)
AI2+
6
AI2-
7
AI1 current/voltage selection jumper
AI1
AI2 current/voltage selection jumper
AI2
Analog output AO1 [Current %]
XA
O
AO1+
1
AO1-
2
Analog output AO2 [Speed %]
AO2+
3
AO2-
4
Drive-to-drive link termination jumper
T
Drive-to-drive link.
XD
2D
B
1
A
2
BGND
3
Safe Torque Off. Both circuits must be closed for the drive to start.
XS
T
O
OUT1
1
OUT2
2
IN1
3
IN2
4
Control panel connection
Memory unit connection
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...