68 Electrical installation
Rotor and rotor cable
1. Check that the generator rotor cable is connected to the generator (terminals K, L and
M), and the stator cable is connected to the generator (terminals U, V and W).
2. Ensure that the other ends of the cables are unconnected.
3. Measure the insulation resistance between each phase conductor and the protective
earth conductor using a measuring voltage of 1 kV DC. Measure both rotor and stator
cables. The insulation resistance of an ABB generator must exceed 100 Mohm
(reference value at 25 °C (77 °F)). For the insulation resistance of other generators,
please consult the manufacturer’s instructions.
Note:
Moisture inside the generator
casing will reduce the insulation resistance. If moisture is suspected, dry the generator
and repeat the measurement.
DC resistor and resistor cable
D150
•
Check that the resistor cable is connected to the resistor and disconnected from the
converter output terminals R+ and R-. At the converter end, connect the R+ and R-
conductors of the resistor cable together.
•
Measure the insulation resistance between the combined conductors and the PE
conductor by using a measuring voltage of 1 kV DC. The insulation resistance must be
higher than 1 Mohm.
D150+D151
Every converter equipped with integrated DC resistor is tested for insulation between the
main circuit and the chassis at the factory (2700 V rms 50 Hz for 1 second). Do not make
any voltage tolerance or insulation resistance tests.
ohm
V
PE
U
W
K
M
L
G
ohm
PE
R+
R-
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...