Planning the electrical installation 65
Protecting the converter against ground faults
in the converter, grid cable, rotor or rotor cable
The rotor-side converter is equipped with an internal ground fault protective function to
protect the converter against ground faults in the generator and rotor cable. The grid-side
converter is equipped with an internal ground fault protective function to protect the
converter against ground faults in the converter or grid cable. This is not a personal safety
or a fire protection feature.
Implementing the emergency stop function
The converter is equipped with emergency stop function of Category 0 (immediate
removal of power) as standard.
For safety reasons, install the emergency stop devices at each operator control station
and at other operating stations where emergency stop may be needed.
See also section
on page
Supplying power for the auxiliary circuits
As standard the converter auxiliary circuit is to be supplied from the power supply network
through an external auxiliary voltage transformer and UPS. The converter is equipped with
terminals for connecting external control voltages (X1 and X2). The circuit breakers are
located in the auxiliary control cubicle of the converter. For information on the power
consumption of auxiliary devices, see section
Auxiliary circuit current consumption
page
.
Uninterrupted auxiliary power supply for the converter (UPS)
The converter is equipped with a 1-phase 230 V AC (50/60 Hz) connection for control
electronics to be supplied by UPS (UPS not included in the ABB delivery). It is
recommended to use an on-line type of UPS the output voltage of which does not depend
on the voltage and frequency of the power supply network. In case of UL and without
C108 or +C109 also 1-phase 50/60 Hz is allowed.
Auxiliary power supply for converter (non-UPS)
The converter is equipped with a 1-phase 230 V AC (50/60 Hz) connection for heating
control logic and cooling fan supply power. In case of UL and without C108 or
+C109 also 1-phase 50/60 Hz is allowed.
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...