58 Planning the electrical installation
Sizes of grounding conductor terminals are listed below.
Conduit
Bridge the joints of the conduits with a ground conductor bonded to the conduit on each
side of the joint. Bond the conduits also to the converter enclosure and generator frame.
Use separate conduits for input power, generator, DC resistors, and control wiring. When
conduit is employed, type MC continuous corrugated aluminum armor cable or shielded
cable is not required. A dedicated ground cable is always required.
Note:
Do not run generator wiring from more than one converter in the same conduit.
Armored cable / shielded power cable
Six conductor (3 phases and 3 ground) type MC continuous corrugated aluminum armor
cable with symmetrical grounds is available from the following suppliers (trade names in
parentheses):
•
Anixter Wire & Cable (Philsheath)
•
BICC General Corp (Philsheath)
•
Rockbestos Co. (Gardex)
•
Oaknite (CLX).
Shielded power cables are available from Belden, Lapp Kabel (ÖLFLEX) and Pirelli,
among others.
Maximum ampere rating of
overcurrent protection for
field wiring conductors
supplying panel
Size of equipment grounding or bonding conductor, minimum
Copper
Aluminum
AWG or kcmil
mm
2
AWG or kcmil
mm
2
15
14
2.1
12
3.3
20
12
3.3
10
5.3
30
10
5.3
8
8.4
40
10
5.3
8
8.4
60
10
5.3
8
8.4
100
8
8.4
6
13.3
200
6
13.3
4
21.2
300
4
21.2
2
33.6
400
3
26.7
1
42.4
500
2
33.6
1/0
53.5
600
1
42.4
2/0
67.4
800
1/0
53.5
3/0
85.0
1000
2/0
67.4
4/0
107.2
1200
3/0
85.0
250 kcmil
127
1600
4/0
107.2
350
177
2000
250 kcmil
127
400
203
2500
350
177
600
304
3000
400
203
600
304
4000
500
253
800
405
5000
700
355
1200
608
6000
800
506
1200
608
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...