132 Technical data
Validating the operation of a safety function
IEC 61508 and EN IEC 62061 require that the final assembler of the machine validates the
operation of the safety function with an acceptance test. The acceptance tests for the
standard safety functions of the converter are described in chapter
. The tests for the optional safety functions are described in the appropriate
option manuals.
The acceptance test must be performed:
•
at initial start-up of the safety function
•
after any changes related to the safety function (wiring, components, settings, etc.)
•
after any maintenance work related to the safety function.
Authorized person
The acceptance test of the safety function must be carried out by an authorized person
with expertise and knowledge of the safety function. The test must be documented and
signed by the authorized person.
Acceptance test reports
Signed acceptance test reports must be stored in the logbook of the machine. The report
shall include documentation of start-up activities and test results, references to failure
reports and resolution of failures. Any new acceptance tests performed due to changes or
maintenance shall be logged into the logbook.
Compliance with the EN 61800-3
The EMC Directive defines the requirements for immunity and emissions of electrical
equipment used within the European Union. The EMC product standard (EN 61800-3)
covers requirements stated for converters.
Definitions
EMC stands for
E
lectro
m
agnetic
C
ompatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment. Likewise,
the equipment must not disturb or interfere with any other product or system within its
locality.
First environment
includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment
includes establishments connected to a network not supplying
domestic premises.
Drive of category C3:
drive of rated voltage less than 1000 V and intended for use in the
second environment and not intended for use in the first environment.
Drive of category C4:
drive of rated voltage equal to or above 1000 V, or rated current
equal to or above 400 A, or intended for use in complex systems in the second
environment.
Category C3
The converter complies with the standard with the following provisions:
1. The generator and control cables are selected as specified (recommended cable
types) in the
Hardware Manual
.
2. The converter is installed according to the instructions given in the
Hardware Manual
.
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...