128 Technical data
DC resistor connection data
See
ABRU-0x DC choppers (+D150) and resistors (+D151) for ACS800-67LC/-77LC/-
87LC wind turbine converters hardware manual
[3AUA0000076494 (English)].
DC connection data
Efficiency
System efficiency is at least 97% at rated current and nominal supply voltage (generator
dependent).
Degree of protection
IP54 as standard. UL Type 12 is available as an option (+C129).
Ambient conditions
Nominal voltage
976 V DC +20%
Maximum operating voltage
< 1211 V DC
DC voltage limits
Overvoltage: 136% x
U
DC
Undervoltage: 50% x
U
DC
Current
See section
Environmental limits for the converter are given below. The converter must be
used in a specified environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 2000 m (6562 ft)
above sea level. Above
1000 m (3281 ft), see
section
on page
-
-
Air temperature
-30 to +55 °C (-22 to
131 °F). Above +45 °C
(+113 °F), see section
on page
frost allowed.
Note:
UL temperature
requirement: max. +40 °C
(+104 °F).
-40 to +70 °C (-40 to
+158 °F)
-40 to +70 °C (-40 to
+158 °F)
Water temperature
See section
on page
.
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
Boards with coating:
Chemical gases: Class
3C2
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class
1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class
2C2
Solid particles: Class 2S2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...