88 Practical examples
Example
ABB wind turbine generator 3.05 MW, stator voltage 12 kV, 60 Hz
Generator type code
AML 630L6A BAFT
Generator type
Slip ring generator
Mounting designation
IM 1001
Protected by enclosure/slip ring unit
IP 54/23
Method of cooling
IC 616
Insulation
Class F
Standards
IEC
Ambient temperature
-20 °C…+50 °C
-30 °C…+50 °C
Altitude, max.
1000 m.a.s.l.
Doubly-fed operation
Duty type
S1
Temp. rise
F (RES)
Connection of stator winding
Star
Rated output
3050 kW
Par. 99.12
Rated power factor
1.0
Par. 99.02
Voltage
12 kV
Par. 99.04
Frequency
60 Hz
Speed
1320 rpm
Par. 99.03
Stator current
134 A
Par. 99.15
Open circuit voltage
1722 V
Rotor voltage
177 V
Rotor current
989 A
Efficiency at rated load with fan
96.1%
Connection of rotor winding
Star
Rotor resistance/phase
0.0035 ohm
Rotor short-circuited
Rated torque
-22753 N·m
Par. 99.06
Load characteristics as induction machine
(2770 kW)
Load % Current A Efficiency % Power factor
100 156 96.4 0.86
75 120 96.4 0.83
50 87 95.9 0.77
Direction of rotation
Uni-directional
Weight of rotor
Approximately 5900 kg
Total weight of generator
13470 kg
Inertia rotor / load
Approximately 400 kgm
2
Bearings
Antifriction
Содержание ACS800-67
Страница 1: ...ABB wind turbine converters System description and start up guide ACS800 67 wind turbine converters ...
Страница 4: ......
Страница 76: ...76 Start up with medium voltage stator ...
Страница 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Страница 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Страница 118: ...118 Tracing the source of warnings limits and faults ...
Страница 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...