Tracing the source of warnings, limits and faults 115
Checking the phase sequence of grid-side converter
voltage measurement
NUIM board in use (grid-side converter control program IXXR72xx)
If an OVERCURRENT fault occurs during the start-up when the operation of the converter
is tested, or if the grid fault ride-through function fails, make the checks described in the
table below.
Action
Check the value of grid-side converter parameter 01.11 MAINS VOLTAGE. Refer to
ACS800 IGBT
supply control program firmware manual
[3AFE68315735 (English)].
If the voltage level is correct, the communication between NUIM board and DDCS channel 2 of the
grid-side converter control board is OK.
Check the phase sequence of the grid-side converter grid voltage measurement:
Monitor the following grid-side converter signals with DriveWindow Datalogger at 1 ms intervals:
138.02 FLUX X NET ACT (measured signal)
138.03 FLUX Y NET ACT (measured signal)
161.04 FLUX X ACT (converter actual signal)
161.05 FLUX Y ACT (converter actual signal).
Start the Datalogger and trigger it manually. Upload Datalogger information. An example view of the
Datalogger is shown below.
If signals 138.02 FLUX X NET ACT and 161.04
FLUX X ACT are in phase and signals 138.03 FLUX
Y NET ACT and 161.04 FLUX Y ACT are in phase, the measurement phase sequence is OK.
Note:
If the signals are not in phase, check the grid voltage measurement cabling of the grid-side
converter measuring unit and correct the phase sequence. See
the converter hardware manual.
Содержание ACS800-67
Страница 1: ...ABB wind turbine converters System description and start up guide ACS800 67 wind turbine converters ...
Страница 4: ......
Страница 76: ...76 Start up with medium voltage stator ...
Страница 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Страница 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Страница 118: ...118 Tracing the source of warnings limits and faults ...
Страница 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...