Technical data
146
Definitions
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3281 ft), or if the ambient temperature e45 °C (+113 °F).
Temperature derating
In the temperature range +45 °C (+113 °F) to +55 °C (+131 °F), the rated output current is decreased
by 0.5% for every additional 1 °C (1.8 °F). The output current is calculated by multiplying the current
given in the rating table by the derating factor.
Example
If the ambient temperature is 55 °C (+131 °F), the derating factor is 100% - 0.5
· 10 °C =
95% or 0.95. The output current is then 0.95 ×
I
2N
or 0.95 ×
I
cont.max
.
U
N
= 690 V
ACS800-17LC-0130-7
106
137
110
102
90
79
75
ACS800-17LC-0170-7
139
206
132
133
132
104
90
ACS800-17LC-0210-7
179
265
200
172
160
134
132
ACS800-17LC-0280-7
237
386
250
228
200
177
160
ACS800-17LC-0390-7
330
604
315
317
315
247
250
ACS800-17LC-0470-7
395
604
400
379
355
295
250
ACS800-17LC-0630-7
530
872
560
509
500
396
400
ACS800-17LC-0950-7
795
1344
800
763
710
595
630
ACS800-17LC-1240-7
1040
1710
1000
998
1000
778
800
ACS800-17LC-1840-7
1540
2538
1600
1478
1400
1152
1200
ACS800-17LC-2430-7
2035
3350
2000
1954
2000
1522
1600
ACS800-17LC-3620-7
3025
4974
3200
2904
2800
2263
2400
ACS800-17LC-4630-7
3878
5802
4000
3723
3600
2901
2800
ACS800-17LC-5300-7
4432
6630
4400
4255
4000
3315
3200
ACS800-17LC-5960-7
4986
7460
5200
4787
4800
3730
3600
PDM 00430970
Nominal ratings
I
cont.max
Continuous rms output current. No overloadability at 45 °C (113 °F).
I
max
Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Typical ratings for no-overload use
P
cont.max
Typical motor power. The power ratings apply to most IEC 60034 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for light-overload use
(10% overloadability)
I
2N
Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
P
N
Typical motor power. The power ratings apply to most IEC 60034 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for heavy-duty use
(50% overloadability)
I
2hd
Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
P
hd
Typical motor power. The power ratings apply to most IEC 60034 motors at nominal voltage
(400, 500 or 690 V).
Drive type
Nominal ratings
No-overload
use
Light-overload use
Heavy-duty use
I
cont.max
I
max
P
contmax
I
2N
P
N
I
2hd
P
hd
A (AC)
A
kW
A
kW
A
kW
%
°C
Содержание ACS800-17LC
Страница 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Страница 4: ......
Страница 10: ...Update notice 6 ...
Страница 18: ...Table of contents 12 ...
Страница 26: ...Safety instructions 20 ...
Страница 32: ...Introduction to the manual 26 ...
Страница 60: ...Hardware description 54 ...
Страница 74: ...Mechanical installation 68 ...
Страница 114: ...Electrical installation 108 ...
Страница 142: ...Maintenance 136 ...
Страница 150: ...Internal cooling circuit 144 ...
Страница 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Страница 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Страница 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...