Start-up
114
Switching the control panel between the supply and inverter units
The control panel is switched between the supply unit and inverter units as follows:
WARNING!
The drive does not stop by pressing the control panel Stop key in remote
control mode.
Changing control to the supply unit
Step
Action
Press…
Display (example)
1.
To enter the Drive Selection Mode
Note:
In local control mode, the inverter unit trips if
parameter 30.02 PANEL LOSS is set to FAULT. Refer to
the appropriate application program firmware manual.
2.
To scroll to ID number 2
3.
To verify the change to the supply unit and display the
warning or fault text
Changing control to the inverter unit
Step
Action
Press…
Display (example)
1.
To enter the Drive Section Mode
2.
To scroll to ID number 1
3.
To verify the change to the inverter unit
DRIVE
ACS 800 0490_3LM
ASXR7xxx
ID-NUMBER 1
ISU 800 0490_3LM
IXXR7xxx
ID-NUMBER 2
ACT
ISU 800 0490_3LM
DC OVERVOLT (3210)
2 -> 380.0 V
*** FAULT ***
DRIVE
ISU 800 0490_3LM
IXXR7xxx
ID-NUMBER 2
ACS 800 0490_3LM
ASXR7xxx
ID-NUMBER 1
ACT
FREQ 0.00 Hz
CURRENT 0.00 A
POWER 0.00 %
1 L -> 0.0 rpm I
Содержание ACS800-17LC
Страница 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Страница 4: ......
Страница 10: ...Update notice 6 ...
Страница 18: ...Table of contents 12 ...
Страница 26: ...Safety instructions 20 ...
Страница 32: ...Introduction to the manual 26 ...
Страница 60: ...Hardware description 54 ...
Страница 74: ...Mechanical installation 68 ...
Страница 114: ...Electrical installation 108 ...
Страница 142: ...Maintenance 136 ...
Страница 150: ...Internal cooling circuit 144 ...
Страница 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Страница 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Страница 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...