Ex24 V power supply for the RMIO board
107
Ex24 V power supply for the RMIO board
What this chapter contains
This chapter describes how to connect ex24 V power supply to the RMIO
board of the motor-side converter. For instructions on how to supply ex24 V
also to the RMIO board of line-side converter, please contact ABB.
When to use
Ex24 V power supply for the RMIO board is recommended if
• the application requires fast start after connecting the input power supply
• fieldbus communication is required when the input power supply is disconnected.
For current consumption of the RMIO board, see chapter
Parameter settings
In Standard Application Program, set parameter 16.9 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.