Electrical installation 83
Control and power supply cables for fan units
1. Route the control and power supply cables through one of the cable entries located in
the floor of the fan unit. Choose either the front or the rear cable entry, according to the
position of the fan cable connector.
2. Connect each cable to the appropriate connector.
Sealing holes in entry plates
•
Seal the gap between cable and entry plate with the supplied two component sealant.
For mixing and applying the sealing compound, follow the instructions on the
packaging.
NOTICE
The control and power supply cables are already prepared in the factory for connection.
1
Front cable entry
2
Rear cable entry
3
Fan cable connectors
For information on connection details, see
1
2
3