Maintenance 141
Start the drive following chapter of “Operation”
Attention:
•
Reform DC-link capacitors in Power modules and spare power modules If the stock
age more than 1year following
2UBB017371_ACS580MV capacitor reforming
instruction
.
ABB provide standard drive startup service package. 400-810-8885
2
All power cables to drive, and from drive to motor are meggered, and measured values are within
the required limits.
Spare parts
1
Sufficient number and correct type of spare parts available.
2
Power supply
1
All auxiliary power supplies from external sources are switched on.
2
All internal circuit breakers of the drive are closed.
3
All grounding devices are removed.
4
All covers are mounted and the doors are closed, locked and / or bolted.
5
There is no run interlock active.
6
MCB is in operating position.
Содержание ACS580MV
Страница 1: ...ABB industrial drives Hardware manual ACS580MV drives 200 kW to 6300 kW 6 kV to 11 kV...
Страница 4: ......
Страница 10: ...10...
Страница 50: ...50 Control system and interfaces...
Страница 52: ...52 Guidelines for planning the electrical installation...
Страница 77: ...Electrical installation 77 Power cable entry from top 1 screen extensions to ground 1...
Страница 90: ...90 Installation checklist...
Страница 125: ...Maintenance 125 5 Disconnect the fiber optic links from the power module 1 Hoist 2 screw M8X20 1 2...
Страница 127: ...Maintenance 127 stops it again 10 Connect the second lifting belts to the lifting eyes provided on the power module...
Страница 142: ...142 Maintenance...
Страница 144: ......
Страница 146: ...Contact us 2UBB004520 Rev E EN 2019 06 27 www abb com drives www abb com drivespartners...