Option 111
SBU Cold commissioning
Set SBU parameter
•
Use the standard AI2 as the RSYC-01 board BUF_OUT signal interface. Select AI2
unit selection to V on the front of the BCON.
•
Set parameters for MSS and MB control.
Set following parameters via drive startup
:
Drive Parameter
setting
Description
16.01 Module 3
type
FIO-01
FIO-01 is added and in position 3 for SBU function.
12.25 AI2 unit
selection
V
Set unit to V
12.27 AI2 min
0V
Set AI2 min value. Voltage range of RSYC-01 BUF OUT is 0~10V.
12.28 AI2 max
10V
Set AI2 max value
16.19 DIO3 function
Output
Select DIO3 as output.
If two signals (open and close) are used for MSS control, this
parameter needs to set.
16.21 DIO3 output
source
P 85.2.14
MSS open command signal is from SBU function SW bit 14.
If two signals (open and close) are used for MSS control, this
parameter needs to set.
16.24 DIO4 function
Output
Select the DIO4 as the output.
If two signals (open and close) are used for MB control, this
parameter needs to set.
16.26 DIO4 output
source
P 85.2.15
MB open command signal is from SBU function SW bit 15.
If two signals (open and close) are used for MB control, this
parameter needs to set.
16.34 RO1 source
P 85.2.12
MSS close command is from SBU function SW bit12
16.37 RO2 source
P 85.2.13
MB close command is from SBU function SW bit13
19.11 Ext1/Ext2
selection
EXT1
Sync to main only works in external control (
EXT1
or
EXT2
).
Содержание ACS580MV
Страница 1: ... ABB INDUSTRIAL DRIVES ACS580MV Commissioning Manual 200kW to 6300 kW 3 3kV to 11 kV ...
Страница 4: ......
Страница 8: ...8 ...
Страница 43: ...Standard Commissioning Process 43 Press the button Load SW and wait till update is finished ...
Страница 45: ...Standard Commissioning Process 45 In this step should select Lab Tools Standalone Installation ...
Страница 60: ...60 Standard Commissioning Process Complete the installation press Finish ...
Страница 83: ...Standard Commissioning Process 83 ...
Страница 96: ...96 Standard Commissioning Process ...
Страница 121: ...Option 121 IO signals ...
Страница 122: ...122 Option Panel control interface System fault ...
Страница 140: ...140 Option ...
Страница 148: ...148 Preventive Maintenance ...