Electrical safety in installation, start-up and maintenance
■
Electrical safety precautions
These electrical safety precautions are for all personnel who do work on the drive, motor
cable or motor.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrician, do not do installation or maintenance work.
Go through these steps before you begin any installation or maintenance work.
1.
Keep the cabinet doors closed when the drive is powered. With the doors open, a risk
of a potentially fatal electric shock, arc flash or high-energy arc blast exists.
2.
Clearly identify the work location and equipment.
3.
Disconnect all possible voltage sources. Make sure that re-connection is not possible.
Lock out and tag out.
•
Open the main disconnecting device of the drive.
•
Open the charging switch if present.
•
Open the disconnector of the supply transformer. (The main disconnecting device
in the drive cabinet does not disconnect the voltage from the AC input power busbars
of the drive cabinet.)
•
Open the auxiliary voltage switch-disconnector (if present), and all other possible
disconnecting devices that isolate the drive from dangerous voltage sources.
•
If you have a permanent magnet motor connected to the drive, disconnect the motor
from the drive with a safety switch or by other means.
•
Disconnect any dangerous external voltages from the control circuits.
•
After you disconnect power from the drive, always wait 5 minutes to let the
intermediate circuit capacitors discharge before you continue.
4.
Protect any other energized parts in the work location against contact.
5.
Take special precautions when close to bare conductors.
6.
Measure that the installation is de-energized. If the measurement requires removal or
disassembly of shrouding or other cabinet structures, obey the local laws and regulations
applicable to live working (including – but not limited to – electric shock and arc
protection).
•
Use a multimeter with an impedance greater than 1 Mohm.
•
Make sure that the voltage between the drive input power terminals (L1, L2, L3)
and the grounding (PE) busbar is close to 0 V.
•
Make sure that the voltage between the drive DC busbars (+ and -) and the
grounding (PE) busbar is close to 0 V.
•
If you have a permanent magnet motor connected to the drive, make sure that the
voltage between the drive output terminals (T1/U, T2/V, T3/W) and the grounding
(PE) busbar is close to 0 V.
20 Safety instructions
3
Содержание ACS580-07
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS580 07 Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 14: ...14 ...
Страница 21: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 Safety instructions 21 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 50: ...50 ...
Страница 62: ...62 ...
Страница 95: ...Electrical installation 95 11 ...
Страница 101: ...Electrical installation 101 11 ...
Страница 114: ...114 ...
Страница 124: ...Note Only 24 V DC can be used for STO Only PNP input configuration can be used 124 Control unit ...
Страница 128: ...128 ...
Страница 134: ...134 ...
Страница 142: ...142 Maintenance ...
Страница 155: ...3 4 5 Maintenance 155 ...
Страница 157: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 157 ...
Страница 161: ...4 5 3 Maintenance 161 ...
Страница 163: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 163 ...
Страница 169: ...1 2 3 5a 5b CR2032 Maintenance 169 ...
Страница 170: ...170 ...
Страница 185: ...Frame R6 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 185 ...
Страница 186: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 186 Technical data ...
Страница 190: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS250 DET A 190 Technical data ...
Страница 191: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 191 ...
Страница 192: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit option F289 192 Technical data ...
Страница 193: ...Frames R6 and R7 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 193 ...
Страница 196: ...Frame R8 Input and motor cable terminal dimensions bottom entry and exit option F289 196 Technical data ...
Страница 199: ...Frames R8 and R9 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 199 ...
Страница 201: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 201 ...
Страница 202: ...Frame R10 Input and motor cable terminal dimensions bottom entry and exit 202 Technical data ...
Страница 203: ...Frame R10 Input and motor cable terminal dimensions bottom entry and exit option E205 Technical data 203 ...
Страница 204: ...Frame R10 Input and motor cable terminal dimensions top entry and exit 204 Technical data ...
Страница 205: ...Frame R10 Input and motor cable terminal dimensions top entry and exit option F289 Technical data 205 ...
Страница 206: ...Frame R11 Input and motor cable terminal dimensions bottom entry and exit 206 Technical data ...
Страница 207: ...Frame R11 Input and motor cable terminal dimensions bottom entry and exit option E205 Technical data 207 ...
Страница 208: ...Frame R11 Input and motor cable terminal dimensions top entry and exit 208 Technical data ...
Страница 209: ...Frame R11 Input and motor cable terminal dimensions top entry and exit option F289 Technical data 209 ...
Страница 217: ...Declaration of Conformity Technical data 217 ...
Страница 218: ...218 Technical data ...
Страница 223: ...Dimension drawings Example dimension drawings are shown below 13 Dimension drawings 223 ...
Страница 224: ...Frames R6 and R7 IP21 UL Type 1 224 Dimension drawings ...
Страница 225: ...Frames R6 and R7 B054 IP42 UL Type 1 Dimension drawings 225 ...
Страница 226: ...Frames R6 and R7 B055 IP54 UL Type 12 226 Dimension drawings ...
Страница 227: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 227 ...
Страница 228: ...Frames R6 and R7 F289 228 Dimension drawings ...
Страница 229: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 229 ...
Страница 230: ...Frames R8 and R9 IP21 230 Dimension drawings ...
Страница 231: ...Frames R8 and R9 B054 IP42 UL Type 1 Dimension drawings 231 ...
Страница 232: ...Frames R8 and R9 B055 IP54 UL Type 12 232 Dimension drawings ...
Страница 233: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 233 ...
Страница 234: ...Frames R8 and R9 F289 234 Dimension drawings ...
Страница 235: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 235 ...
Страница 236: ...Frames R10 and R11 IP21 236 Dimension drawings ...
Страница 237: ...Frames R10 and R11 B054 IP42 UL Type 1 Dimension drawings 237 ...
Страница 238: ...Frames R10 and R11 B055 IP54 UL Type 12 238 Dimension drawings ...
Страница 239: ...Frames R10 and R11 F289 T Dimension drawings 239 ...
Страница 240: ...Frames R10 and R11 H351 H353 240 Dimension drawings ...
Страница 241: ...Frames R10 and R11 B054 IP42 UL type 1 H351 H353 T Dimension drawings 241 ...
Страница 242: ...Frames R10 and R11 B055 IP54 UL type 12 H351 H353 T 242 Dimension drawings ...
Страница 257: ... Declaration of conformity The Safe torque off function 257 ...
Страница 269: ...Setting Parameter 1 s 15 09 RO4 OFF delay Optional I O extension modules 269 ...