Optional I/O extension modules 159
Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
•
make sure that the value of both parameter 15.02 Detected extension module and
parameter 15.01Extension module type is CMOD-01.
If warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of parameter 15.02 Detected extension module is
CMOD-01.
•
set parameter 15.01 Extension module type to CMOD-01.
You can now see the parameters of the extension module in parameter group 15 I/O
extension module.
3. Set the parameters of the extension module to applicable values.
Examples are given below.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module indicate the
motor speed 0... 1500 rpm with a frequency range of 0...10000 Hz.
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
Parameter
Setting
15.07 RO4 source
Reverse
15.08 RO4 ON delay
1 s
15.09 RO4 OFF delay
1 s
Parameter
Setting
15.22 DO1 configuration
Digital output
15.23 DO1 source
Reverse
15.24 DO1 ON delay
1 s
15.25 DO1 OFF delay
1 s
Parameter
Setting
15.22 DO1 configuration
Frequency output
15.33 Freq out 1 source
01.01
15.34 Freq out 1 src min
0
15.35 Freq out 1 src max
1500.00
15.36 Freq out 1 at src min
1000 Hz
15.37 Freq out 1 at src max
10000 Hz
Содержание ACS580-07-0495A-4
Страница 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Страница 4: ......
Страница 8: ...4 Update notice ...
Страница 16: ...12 ...
Страница 24: ...20 Safety instructions ...
Страница 42: ...38 Operation principle and hardware description ...
Страница 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Страница 82: ...78 Electrical installation ...
Страница 102: ...98 Fault tracing ...
Страница 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Страница 115: ...Maintenance 111 R10 and R11 9 10 ...
Страница 116: ...112 Maintenance R10 and R11 11 ...
Страница 117: ...Maintenance 113 R10 and R11 12b 12a ...
Страница 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Страница 126: ...122 Technical data Input and motor cable terminal dimensions of frame R10 Bottom entry and exit ...
Страница 127: ...Technical data 123 Input and motor cable terminal dimensions of frame R11 Bottom entry and exit ...
Страница 134: ...130 Technical data ...
Страница 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Страница 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Страница 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Страница 140: ...136 Dimension drawings ...
Страница 152: ...148 Safe torque off function ...
Страница 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...