16 EN – R6…R9 Quick installation guide
R0-
R4
R6-
R9
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
Default I/O connections
Default I/O connections of the ABB Standard macro are shown below.
max.
500 ohm
1…10 kohm
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency/speed reference
: 0…10 V
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Not configured
6
AGND
Analog input circuit common
7
AO1
Output frequency:
0…20 mA
8
AO2
Output current:
0…20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Forward (0) / Reverse (1)
15
DI3
Constant frequency/speed selection
16
DI4
Constant frequency/speed selection
17
DI5
Ramp set 1 (0) / Ramp set 2 (1)
18
DI6
Not configured
X6, X7, X8
Relay outputs
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
B+
Embedded Modbus RTU (EIA-485)
30
A-
31
DGND
S4
TERM
Serial data link termination switch
S5
BIAS
Serial data link bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function
in
ACS580-01 (0.75
to 250 kW, 1.0 to 350 hp) hardware manual
(3AXD50000044794 [English]).
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in Ext. 24V AC/DC input to power up the control unit
when the main supply is disconnected.
41
24 V AC/DC- in
Total load capacity of the Auxiliary voltage 24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes: 0.14…2.5 mm
2
(26…16 AWG): All terminals
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Содержание ACS580-01 Series
Страница 6: ...2019 ABB Oy All Rights Reserved...
Страница 10: ...10 R6 R9 Quick installation guide R0 R3 R6 R9 EN DA DE ES FI FR IT NL PL PT RU SV TR ZH...
Страница 18: ...18 EN R6 R9 Quick installation guide R0 R4 R6 R9 R6 R9 EN DA DE ES FI FR IT NL PL PT RU SV TR ZH...