Fieldbus control through the embedded fieldbus interface (EFB) 465
Error code registers (holding registers 400090…400100)
These registers contain information about the last query. The error register is cleared
when a query has finished successfully.
Reference Name
Description
400090
Reset Error Registers
1 = Reset internal error registers (91…95). 0 = Do
nothing.
400091
Error Function Code
Function code of the failed query.
400092
Error Code
Set when exception code 04h is generated (see table
above).
• 00h No error
• 02h Low/High limit exceeded
• 03h Faulty Index: Unavailable index of an array
parameter
• 05h Incorrect Data Type: Value does not match the
data type of the parameter
• 65h General Error: Undefined error when handling
query
400093
Failed Register
The last register (discrete input, coil, input register or
holding register) that failed to be read or written.
400094
Last Register Written
Successfully
The last register (discrete input, coil, input register or
holding register) that was written successfully.
400095
Last Register Read
Successfully
The last register (discrete input, coil, input register or
holding register) that was read successfully.
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...