ACS550 User’s Manual
247
Diagnostics
24
OVERSPEED
Motor speed is greater than 120% of the larger (in magnitude) of 2001
MINIMUM
SPEED
or 2002
MAXIMUM
SPEED
. Check for and correct:
• Parameter settings for 2001 and 2002.
• Adequacy of motor braking torque.
• Applicability of torque control.
• Brake chopper and resistor.
25
RESERVED
Not used.
26
DRIVE
ID
Internal fault. Configuration Block Drive ID is not valid. Contact your local
ABB representative.
27
CONFIG
FILE
Internal configuration file has an error. Contact your local ABB
representative.
28
SERIAL
1
ERR
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
).
as appropriate).
• Poor connections and/or noise on line.
29
EFB
CON
FILE
Error in reading the configuration file for the embedded fieldbus.
30
FORCE
TRIP
Fault trip forced by the fieldbus. See the fieldbus User’s Manual.
31
EFB
1
Fault code reserved for the embedded fieldbus (EFB) protocol application.
The meaning is protocol dependent.
32
EFB
2
33
EFB
3
34
MOTOR
PHASE
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
35
OUTP
WIRING
Possible power wiring error detected. When the drive is not running it
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltage is NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
WIRING
FAULT
.
36
INCOMPATIBLE
SW
The drive cannot use the software.
• Internal fault.
• The loaded software is not compatible with the drive.
• Call support representative.
37
CB
OVERTEMP
Drive control board is overheated. The fault trip limit is 88 °C. Check for and
correct:
• Excessive ambient temperature.
• Fan failure.
• Obstructions in the air flow.
Not for drives with an OMIO control board.
38
USER
LOAD
CURVE
Condition defined by parameter 3701
USER
LOAD
C
MODE
has been valid
longer than the time defined by 3703
USER
LOAD
C
TIME
.
Fault
code
Fault name in
panel
Description and recommended corrective action
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...