ACS550 User’s Manual
117
35 =
COMM
– Energize relay based on input from fieldbus communication.
• Fieldbus writes binary code in parameter 0134 that can energize relay 1…relay 6 according to the following:
• 0 = De-energize relay, 1 = Energize relay.
36 =
COMM
(-1) – Energize relay based on input from fieldbus communication.
• Fieldbus writes binary code in parameter 0134 that can energize relay 1…relay 6 according to the following:
• 0 = De-energize relay, 1 = Energize relay.
37 =
TIMED
FUNC
1 – Energize relay when Timed Function 1 is active. See
38…40 =
TIMED
FUNC
2…4 – Energize relay when Timed Function 2…4 is active. See
TIMED
FUNC
1 above.
41 =
MNT
TRIG
FAN
– Energize relay when cooling fan counter is triggered. See
42 =
MNT
TRIG
REV
– Energize relay when revolutions counter is triggered. See
.
43 =
MNT
TRIG
RUN
– Energize relay when run time counter is triggered. See
.
44 =
MNT
TRIG
MWH
– Energize relay when MWh counter is triggered. See
.
46 =
START
DELAY
– Energize relay when a start delay is active.
47 =
USER
LOAD
C
– Energize relay when a user load curve fault or alarm occurs.
52 =
JOG
ACTIVE
– Energize relay when the jogging function is active.
1402
RELAY OUTPUT 2
Defines the event or condition that activates relay 2 – what relay output 2 means.
• See 1401
RELAY
OUTPUT
1.
1403
RELAY OUTPUT 3
Defines the event or condition that activates relay 3 – what relay output 3 means.
• See 1401
RELAY
OUTPUT
1.
1404
RO 1 ON DELAY
Defines the switch-on delay for relay 1.
• On / off delays are ignored when relay output 1401 is set to PFC.
1405
RO 1 OFF DELAY
Defines the switch-off delay for relay 1.
• On / off delays are ignored when relay output 1401 is set to PFC.
1406
RO 2 ON DELAY
Defines the switch-on delay for relay 2.
• See
RO
1
ON
DELAY
.
1407
RO 2 OFF DELAY
Defines the switch-off delay for relay 2.
• See
RO
1
OFF
DELAY
.
1408
RO 3 ON DELAY
Defines the switch-on delay for relay 3.
• See
RO
1
ON
DELAY
.
Code Description
Par. 0134
Binary
RO6 RO5 RO4 RO3 RO2 RO1
0
000000
0
0
0
0
0
0
1
000001
0
0
0
0
0
1
2
000010
0
0
0
0
1
0
3
000011
0
0
0
0
1
1
4
000100
0
0
0
1
0
0
5…62
…
…
…
…
…
…
…
63
111111
1
1
1
1
1
1
Par. 0134 Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
1
1
1
1
1
1
1
000001
1
1
1
1
1
0
2
000010
1
1
1
1
0
1
3
000011
1
1
1
1
0
0
4
000100
1
1
1
0
1
1
5…62
…
…
…
…
…
…
…
63
111111
0
0
0
0
0
0
1404
ON
DELAY
1405
OFF
DELAY
Control event
Relay status
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...