
36
ACS550 User’s Manual
Start-Up
•
Set not found – You are attempting to download a data set that was not defined in
the backup. The remedy is to manually define the set, or upload the set from a
drive that has the desired set definitions.
•
Par lock – The remedy is to unlock the parameter set (parameter 1602).
•
Incompat drive/model – The remedy is to perform backups only between drives of
the same type (ACS/industrial or ACH/HVAC) and the same model (all ACS550).
•
Too many differences – The remedy is to manually define a new set, or upload the
set from a drive that more closely resembles the target drive.
I/O Settings Mode
Use the I/O Setting mode to check (and edit) the setting at any I/O terminal.
1. Select I/O SETTINGS in the Main Menu.
2. Press UP/DOWN to step to the desired I/O group, for example, digital inputs.
3. Press ENTER.
4. Press UP/DOWN to step to a particular item, for example DI1.
After a brief pause, the displays shows the current setting for the selection.
5. Press EDIT.
6. Press UP/DOWN to select a new setting.
7. Press SAVE to save.