146
ACS550 User’s Manual
Start-Up
8124
ACC IN AUX STOP
Sets the PFC acceleration time for a zero-to-maximum
frequency ramp. This PFC acceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched off.
• Replaces the acceleration ramp defined in Group 22:
Accel / Decel.
• Applies only until the output of the regulated motor
increases by an amount equal to the output of the
switched off auxiliary motor. Then the acceleration ramp
defined in Group 22: Accel / Decel applies.
0 =
NOT
SEL
.
0.1…1800 = Activates this function using the value
entered as the acceleration time.
• A = speed regulated motor accelerating using Group 22
parameters (2202 or 2205).
• B = speed regulated motor decelerating using Group 22
parameters (2203 or 2206).
• At aux. motor start, speed regulated motor decelerates
using 8125
DEC
IN
AUX
START
.
• At aux. motor stop, speed regulated motor accelerates
using 8124
ACC
IN
AUX
STOP
.
8125
DEC IN AUX START
Sets the PFC deceleration time for a maximum-to-zero
frequency ramp. This PFC deceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched on.
• Replaces the deceleration ramp defined in Group 22
ACCEL / DECEL.
• Applies only until the output of the regulated motor
decreases by an amount equal to the output of the
auxiliary motor. Then the deceleration ramp defined in
Group 22 ACCEL / DECEL applies.
0 =
NOT
SEL
.
0.1…1800 = Activates this function using the value
entered as the deceleration time.
8126
TIMED AUTOCHNG
Sets the autochange using the Timer function. See parameter 8119
AUTOCHANGE
LEVEL
.
0 =
NOT
SEL
.
1 =
TIMER
FUNCTION
1 – Enables autochange when Timer function 1 is active.
2…4 =
TIMER
FUNCTION
2…4 – Enables autochange when Timer function 2…4 is active.
8127
MOTORS
Sets the actual number of PFC controlled motors (maximum 7 motors, 1 speed regulated, 3 connected direct-on-line
and 3 spare motors).
• This value includes also the speed regulated motor.
• This value must be compatible with number of relays allocated to PFC if the autochange function is used.
• If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to
PFC but it needs to be included in this value.