ACS510 User’s Manual
Start-Up
2209
RAMP INPUT ZERO
Defines control for forcing the ramp input to zero.
0 =
NOT
SEL
1 =
DI
1 – Defines digital input
DI
1 as the control for forcing the ramp input to zero.
• Activating the digital input forces ramp input to zero. Ramp output will ramp to zero according to the currently
used ramp time, after which it will stay at zero.
• De-activating the digital input: ramp resumes normal operation.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for forcing the ramp input to zero.
• See
DI
1 above.
7 =
COMM
– Defines bit 10 of the Command Word 1 as the control for ramp pair selection.
• The Command Word is parameter 0301, which is supplied through fieldbus communication.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for forcing the ramp input to zero.
• De-activating the digital input forces ramp input to zero.
• Activating the digital input: ramp resumes normal operation.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for forcing the ramp function
generator input to zero.
• See
DI
1(
INV
) above.