52
ACS510 User’s Manual
Start-Up
Complete Parameter List for ACS510
The following table lists all parameters. Table header abbreviations are:
• S
=
Parameters can be modified only when the drive is stopped.
• User = Space to enter desired parameter values
Some values vary depending on the drive software options. This is indicated by
“+N688:” or “+N689 in the table below. Refer to the type code on the drive namplate.
For example ACS510-01...+N688 .
Code
Name
Range
Resolution
Default
User S
Group 99: Start-Up Data
9901
LANGUAGE
0…3
1
0
9902
APPLIC
MACRO
-3…7, 15
1
1
9
9905
MOTOR
NOM
VOLT
200…600 V /
1 V
400 V
9
9906
MOTOR
NOM
CURR
0.2*I
2n
…2.0*I
2n
0.1 A
1.0*I
2n
9
9907
MOTOR
NOM
FREQ
10.0…500.0 Hz /
+N688:10.0...50.0 Hz /
+N689:10.0...55.0 Hz
0.1 Hz
50.0 Hz /
+N688:50.0 Hz /
+N689:55.0 Hz
9
9908
MOTOR
NOM
SPEED
50…30,000 rpm
1 rpm
Size dependent
9
9909
MOTOR
NOM
POWER
0.2…3.0*P
n
0.1 kW
1.0 * P
n
9
Group 01: Operating Data
0101
SPEED & DIR
-30000…30000 rpm
1 rpm
-
0102
SPEED
0…30000 rpm
1 rpm
-
0103
OUTPUT
FREQ
0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz
-
0104
CURRENT
0…2.0*I
2n
0.1 A
-
0105
TORQUE
-200.0…200.0%
0.1%
-
0106
POWER
-2.0…2.0*P
n
0.1 kW
-
0107
DC
BUS
VOLTAGE
0…2.5*V
dN
1 V
-
0109
OUTPUT
VOLTAGE
0…2.0*V
dN
1 V
-
0110
DRIVE
TEMP
0.0…150.0
°
C
0.1
°
C
-
0111
EXTERNAL
REF
1
0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz
-
0112
EXTERNAL
REF
2
0.0…100.0%
0.1%
-
0113
CTRL
LOCATION
0 = local, 1 = ext1, 2 = ext2
1
-
0114
RUN
TIME
(
R
)
0…9999 h
1 h
0 h
0115
KWH
COUNTER
(
R
)
0…9999 kWh
1 kWh
-
0116
APPL
BLK
OUTPUT
0.0…100.0% 0.1%
-
0118
DI
1-3
STATUS
000…111 (0…7 decimal)
1
-
0119
DI
4-6
STATUS
000…111 (0…7 decimal)
1
-
0120
AI
1
0.0…100.0%
0.1%
-
0121
AI
2
0.0…100.0%
0.1%
-
0122
RO
1-3
STATUS
000…111 (0…7 decimal)
1
-
0123
RO
4-6
STATUS
000…111 (0…7 decimal)
1
-
0124
AO
1
0.0…20.0 mA
0.1 mA
-