ACS510 User’s Manual
181
Fieldbus Adapter
Relay Output Control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
1. More than 3 relays requires the addition of a relay extension module.
Note!
Relay status feedback occurs without configuration as defined below.
Analog Output Control
Using the fieldbus for analog output control (e.g. PID setpoint) requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1607
PARAM
SAVE
1 (
SAVE
)
Saves altered parameters to memory (then
value returns to 0).
Drive Parameter
Value
Description
Protocol
Reference
1401
RELAY
OUTPUT
1
35 (
COMM
)
36 (
COMM
(-1))
Relay Output 1 controlled by fieldbus.
1402
RELAY
OUTPUT
2
Relay Output 2 controlled by fieldbus.
1403
RELAY
OUTPUT
3
Relay Output 3 controlled by fieldbus.
1410
1
RELAY
OUTPUT
4
Relay Output 4 controlled by fieldbus.
1411
1
RELAY
OUTPUT
5
Relay Output 5 controlled by fieldbus.
1412
1
RELAY
OUTPUT
6
Relay Output 6 controlled by fieldbus.
Drive Parameter
Value
Protocol Reference
0122
RO
1-3
STATUS
Relay 1…3 status.
0123
RO
4-6
STATUS
Relay 4…6 status.
Drive Parameter
Value
Description
Protocol
Reference
1501
AO
1
CONTENT
SEL
135 (
COMM
VALUE
1) Analog Output 1 controlled by
writing to parameter 0135.
–
0135
COMM
VALUE
1
–
1502
…
1505
AO
1
CONTENT
MIN
…
MAXIMUM
AO
1
Set appropriate
values.
Used for scaling
–
1506
FILTER
AO
1
Filter time constant for
AO
1.
–
1507
AO
2
CONTENT
SEL
136 (
COMM
VALUE
2) Analog Output 2 controlled by
writing to parameter 0136.
–
0136
COMM
VALUE
2
–
Drive Parameter
Value
Description
Protocol
Reference