fault current during the disconnection time of the protective device. The cross-sectional area
of the protective conductor can either be selected from the table below or calculated according
to 543.1 of IEC 60364-5-54.
This table shows the minimum cross-sectional area of the protective conductor related to
the phase conductor size according to IEC 61800-5-1 when the phase conductor and the
protective conductor are made of the same metal. If this is not so, the cross-sectional area
of the protective earthing conductor shall be determined in a manner which produces a
conductance equivalent to that which results from the application of this table.
Minimum cross-sectional area of the corresponding
protective conductor
S
p
(mm
2
)
Cross-sectional area of the phase conductors
S (mm
2
)
S
1)
,
2)
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S
1) Drive safety standard IEC/EN 61800-5-1:
• use a protective earth conductor with a cross-section of at least 10 mm
2
(8 AWG) Cu or 16 mm
2
(6 AWG) Al, or
• use a second protective earth conductor of the same cross-sectional area as the original protective earthing conductor,
or
• use a device which automatically disconnects the supply if the protective earth conductor breaks.
2) Drive safety standard IEC/EN 61800-5-1: If the protective earth conductor is separate (ie, it does not form part of the input
power cable or the input power cable enclosure), the cross section must be at least:
• 2.5 mm
2
(14 AWG) when the conductor is mechanically protected, or
• 4 mm
2
(12 AWG) when the conductor is not mechanically protected.
■
Typical power cable sizes
See the technical data.
■
Power cable types
Preferred power cable types
This section presents the preferred cable types. Make sure that the selected cable type also
complies with local/state/country electrical codes.
Use as motor cabling
Use as input power cabling
Cable type
Yes
Yes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and concentric PE conductor as
shield (or armor)
Yes
Yes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and symmetrically constructed PE
conductor and a shield (or armor)
Guidelines for planning the electrical installation 41
Содержание ACS480
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS480 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 23: ...See https library abb com en for all ABB product documentation on the Internet Introduction to the manual 23 ...
Страница 24: ...24 ...
Страница 34: ...34 ...
Страница 122: ...122 ...
Страница 124: ...Frame R1 Frame R1 front side IP20 UL type open 124 Dimension drawings ...
Страница 125: ... Frame R1 bottom rear IP20 UL type open Dimension drawings 125 ...
Страница 126: ... Frame R1 front side UL type 1 kit installed 126 Dimension drawings ...
Страница 127: ... Frame R1 bottom rear UL type 1 kit installed Dimension drawings 127 ...
Страница 128: ...Frame R2 Frame R2 front side IP20 UL type open 128 Dimension drawings ...
Страница 129: ... Frame R2 bottom rear IP20 UL type open Dimension drawings 129 ...
Страница 130: ... Frame R2 front side UL type 1 kit installed 130 Dimension drawings ...
Страница 131: ... Frame R2 bottom rear UL type 1 kit installed Dimension drawings 131 ...
Страница 132: ...Frame R3 Frame R3 front side IP20 UL type open 132 Dimension drawings ...
Страница 133: ... Frame R3 bottom rear IP20 UL type open Dimension drawings 133 ...
Страница 134: ... Frame R3 front side UL type 1 kit installed 134 Dimension drawings ...
Страница 135: ... Frame R3 bottom rear UL type 1 kit installed Dimension drawings 135 ...
Страница 136: ...Frame R4 Frame R4 front side IP20 UL type open 136 Dimension drawings ...
Страница 137: ... Frame R4 bottom rear IP20 UL type open Dimension drawings 137 ...
Страница 138: ... Frame R4 front side UL type 1 kit installed 138 Dimension drawings ...
Страница 139: ... Frame R4 bottom rear UL type 1 kit installed Dimension drawings 139 ...
Страница 140: ...140 ...
Страница 163: ... Declaration of conformity The Safe torque off function 163 ...
Страница 164: ...164 ...
Страница 172: ...Dimensions 172 BIO 01 I O extension module ...
Страница 178: ...178 ...