Altitude derating: The derating factor for 1500 m is
.
The derated drive output current becomes
Surrounding air temperature derating: From the table, the derating factor for 55 °C
surrounding air temperature is
The derated drive output current becomes
Example 1, UL (NEC): How to calculate the derated current
Drive type is ACS480-04-014A-4, which has drive output current of 14 A. Calculate the
derated drive output current (
I
N
) at 4 kHz switching frequency, at 6000 ft (1829 m) altitude
and at 131 °F (55 °C) surrounding air temperature.
Switching frequency derating: From the table, no derating is needed at 4 kHz.
Altitude derating: The derating factor for 6000 ft is
The derated drive output current becomes
Surrounding air temperature derating: The derating factor for 131 °F surrounding air
temperature is
The derated drive output current becomes
Example 2, IEC: How to calculate the required drive
If your application requires a nominal motor current of 6.0 A at 8 kHz switching frequency,
the supply voltage is 400 V and the drive is situated at 1800 m altitude and at 35 °C
surrounding air temperature, calculate the required drive size.
Altitude derating: The derating factor for 1800 m is
.
Surrounding air temperature derating: No derating needed for 35 °C surrounding air
temperature.
To determine if the derated current of a drive is enough for the application, multiply the
nominal drive output current (
I
N
) by all the applicable derating factors. For example, drive
type ACS480-04-12A7-4 has a nominal output current of 12.6 A. From the table, the switching
frequency derating for this drive type is 0.68 at 8 kHz. Calculate the derated drive output
current:
Technical data 99
Содержание ACS480
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS480 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 23: ...See https library abb com en for all ABB product documentation on the Internet Introduction to the manual 23 ...
Страница 24: ...24 ...
Страница 34: ...34 ...
Страница 122: ...122 ...
Страница 124: ...Frame R1 Frame R1 front side IP20 UL type open 124 Dimension drawings ...
Страница 125: ... Frame R1 bottom rear IP20 UL type open Dimension drawings 125 ...
Страница 126: ... Frame R1 front side UL type 1 kit installed 126 Dimension drawings ...
Страница 127: ... Frame R1 bottom rear UL type 1 kit installed Dimension drawings 127 ...
Страница 128: ...Frame R2 Frame R2 front side IP20 UL type open 128 Dimension drawings ...
Страница 129: ... Frame R2 bottom rear IP20 UL type open Dimension drawings 129 ...
Страница 130: ... Frame R2 front side UL type 1 kit installed 130 Dimension drawings ...
Страница 131: ... Frame R2 bottom rear UL type 1 kit installed Dimension drawings 131 ...
Страница 132: ...Frame R3 Frame R3 front side IP20 UL type open 132 Dimension drawings ...
Страница 133: ... Frame R3 bottom rear IP20 UL type open Dimension drawings 133 ...
Страница 134: ... Frame R3 front side UL type 1 kit installed 134 Dimension drawings ...
Страница 135: ... Frame R3 bottom rear UL type 1 kit installed Dimension drawings 135 ...
Страница 136: ...Frame R4 Frame R4 front side IP20 UL type open 136 Dimension drawings ...
Страница 137: ... Frame R4 bottom rear IP20 UL type open Dimension drawings 137 ...
Страница 138: ... Frame R4 front side UL type 1 kit installed 138 Dimension drawings ...
Страница 139: ... Frame R4 bottom rear UL type 1 kit installed Dimension drawings 139 ...
Страница 140: ...140 ...
Страница 163: ... Declaration of conformity The Safe torque off function 163 ...
Страница 164: ...164 ...
Страница 172: ...Dimensions 172 BIO 01 I O extension module ...
Страница 178: ...178 ...