Action
Test the operation of the STO function when the motor is running.
• Start the drive and make sure the motor is running.
• Open the STO circuit. The motor should stop. The drive generates an indication if one is defined for
the 'running' state in parameter
31.22
(see the firmware manual).
• Reset any active faults and try to start the drive.
• Make sure that the motor stays at a standstill and the drive operates as described above in testing
the operation when the motor is stopped.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the failure detection of the drive. The motor can be stopped or running.
• Open the 1st channel of the STO circuit (wire coming to IN1). If the motor was running, it should
coast to a stop. The drive generates a
FA81 Safe Torque Off 1 loss
fault indication (see the firmware
manual).
• Give a start command to verify that the STO function blocks the drive's operation. The motor should
not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
• Open the 2nd channel of the STO circuit (wire coming to IN2). If the motor was running, it should
coast to a stop. The drive generates a
FA82 Safe Torque Off 2 loss
fault indication (see the firmware
manual).
• Give a start command to verify that the STO function blocks the drive's operation. The motor should
not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Document and sign the acceptance test report which verifies that the safety function is safe and accepted
for operation.
The Safe torque off function 157
Содержание ACS480
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS480 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 23: ...See https library abb com en for all ABB product documentation on the Internet Introduction to the manual 23 ...
Страница 24: ...24 ...
Страница 34: ...34 ...
Страница 122: ...122 ...
Страница 124: ...Frame R1 Frame R1 front side IP20 UL type open 124 Dimension drawings ...
Страница 125: ... Frame R1 bottom rear IP20 UL type open Dimension drawings 125 ...
Страница 126: ... Frame R1 front side UL type 1 kit installed 126 Dimension drawings ...
Страница 127: ... Frame R1 bottom rear UL type 1 kit installed Dimension drawings 127 ...
Страница 128: ...Frame R2 Frame R2 front side IP20 UL type open 128 Dimension drawings ...
Страница 129: ... Frame R2 bottom rear IP20 UL type open Dimension drawings 129 ...
Страница 130: ... Frame R2 front side UL type 1 kit installed 130 Dimension drawings ...
Страница 131: ... Frame R2 bottom rear UL type 1 kit installed Dimension drawings 131 ...
Страница 132: ...Frame R3 Frame R3 front side IP20 UL type open 132 Dimension drawings ...
Страница 133: ... Frame R3 bottom rear IP20 UL type open Dimension drawings 133 ...
Страница 134: ... Frame R3 front side UL type 1 kit installed 134 Dimension drawings ...
Страница 135: ... Frame R3 bottom rear UL type 1 kit installed Dimension drawings 135 ...
Страница 136: ...Frame R4 Frame R4 front side IP20 UL type open 136 Dimension drawings ...
Страница 137: ... Frame R4 bottom rear IP20 UL type open Dimension drawings 137 ...
Страница 138: ... Frame R4 front side UL type 1 kit installed 138 Dimension drawings ...
Страница 139: ... Frame R4 bottom rear UL type 1 kit installed Dimension drawings 139 ...
Страница 140: ...140 ...
Страница 163: ... Declaration of conformity The Safe torque off function 163 ...
Страница 164: ...164 ...
Страница 172: ...Dimensions 172 BIO 01 I O extension module ...
Страница 178: ...178 ...