Actual signals and parameters
233
AI2 JOY
Analog input AI2 as joystick. The minimum input signal runs the motor at the
maximum reference in the reverse direction, the maximum input at the
maximum reference in the forward direction. Minimum and maximum
references are defined by parameters
REF1 MIN and
REF1 SELECT selection AI1/JOYST for more
information.
-0.5
AI1 JOY
See selection AI2 JOY.
-0.4
AI2
Analog input AI2
-0.3
AI1
Analog input AI1
-0.2
KEYPAD
Control panel
-0.1
0.0 …100.0%
Constant speed
8421
ST1 COMMANDS
Selects the start, stop and direction for state 1. Parameter
EXT2
COMMANDS must be set to SEQ PROG.
Note:
If change of direction of rotation is required, parameter
DIRECTION must be set to REQUEST.
DRIVE STOP
DRIVE STOP
Drive coast or ramps to stop depending on parameter
STOP
FUNCTION setting.
0
START FRW
Rotation of direction is fixed to forward. If the drive is not already running, it is
started according to parameter
START FUNCTION settings.
1
START REV
Rotation of direction is fixed to reverse. If the drive is not already running, it is
started according to parameter
START FUNCTION settings.
2
8422
ST1 RAMP
Selects the acceleration/deceleration ramp time for sequence programming
state 1, i.e. defines the rate of the reference change.
0
-0.2/-0.1/
0.0…1800.0 s
Time
When value is set to -0.2 ramp pair 2 is used. Ramp pair 2 is defined by
parameters
…
.
When value is set to -0.1 ramp pair 1 is used. Ramp pair 1 is defined by
parameters
…
.
With ramp pair 1/2, parameter
ACC/DEC 1/2 SEL must be set to SEQ
...
1 = 0.1 s
8423
ST1 OUT CONTROL
Selects the relay, transistor and analog output control for sequence
programming state 1.
The relay/transistor output control must be activated by setting parameter
RELAY OUTPUT 1 /
DO SIGNAL to SEQ PROG. Analog output
control must be activated by parameter group
.
Analog output control values can be monitored with signal
SEQ PROG
AO VAL.
AO=0
R=0,D=1,AO=0
Relay output is de-energized (opened), transistor output is energized and
analog output is cleared.
-0.7
R=1,D=0,AO=0
Relay output is energized (closed), transistor output is de-energized and
analog output is cleared.
-0.6
R=0,D=0,AO=0
Relay and transistor outputs are de-energized (opened) and analog output
value is set to zero.
-0.5
RO=0,DO=0
Relay and transistor outputs are de-energized (opened) and analog output
control is frozen to the previously set value.
-0.4
RO=1,DO=1
Relay and transistor outputs are energized (closed) and analog output
control is frozen to the previously set value.
-0.3
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......