Actual signals and parameters
219
4022
SLEEP SELECTION
Activates the sleep function and selects the source for the activation input.
See section
Sleep function for the process PID (PID1) control
on page
NOT SEL
NOT SEL
No sleep function selected
0
DI1
The function is activated/deactivated through digital input DI1.1 = activation,
0 = deactivation.
The internal sleep criteria set by parameters
PID SLEEP LEVEL and
WAKE-UP DEV are not effective. The sleep start and stop delay
parameters
PID SLEEP DELAY and
WAKE-UP DELAY are
effective.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
INTERNAL
Activated and deactivated automatically as defined by parameters
PID
SLEEP LEVEL and
WAKE-UP DEV.
7
DI1(INV)
The function is activated/deactivated through inverted digital input DI1.
1 = deactivation, 0 = activation.
The internal sleep criteria set by parameters
PID SLEEP LEVEL and
WAKE-UP DEV are not effective. The sleep start and stop delay
parameters
PID SLEEP DELAY and
WAKE-UP DELAY
are
effective.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
4023
PID SLEEP LEVEL
Defines the start limit for the sleep function. If the motor speed is below a set
level (
4023
) longer than the sleep delay (
), the drive shifts to the
sleeping mode: The motor is stopped and the control panel shows alarm
message PID SLEEP.
Parameter
SLEEP SELECTION must be set to INTERNAL.
0
0.0…500.0 Hz /
0…30000 rpm
Sleep start level
1 = 0.1 Hz /
1 rpm
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Start
t < 4024
t
t > 4024
t
Stop
4023
4026
PID reference
PID output level
4025
PID process feedback
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......