Actual signals and parameters
191
2304
ACC
COMPENSATION
Defines the derivation time for acceleration/(deceleration) compensation. In
order to compensate inertia during acceleration a derivative of the reference
is added to the output of the speed controller. The principle of a derivative
action is described for parameter
DERIVATION TIME.
Note:
As a general rule, set this parameter to the value between 50 and
100% of the sum of the mechanical time constants of the motor and the
driven machine. (The speed controller Autotune Run does this automatically,
see parameter
AUTOTUNE RUN.)
The figure below shows the speed responses when a high inertia load is
accelerated along a ramp.
0
0.00…600.00 s
Time
1 = 0.01 s
2305
AUTOTUNE RUN
Start automatic tuning of the speed controller. Instructions:
- Run the motor at a constant speed of 20 to 40% of the rated speed.
- Change the autotuning parameter 2305 to ON.
Note:
The motor load must be connected to the motor.
OFF
OFF
No autotuning
0
ON
Activates the speed controller autotuning. The drive
- accelerates the motor.
- calculates values for proportional gain, integration time and acceleration
compensation (parameter
INTEGRATION TIME and
ACC COMPENSATION
values).
Setting is automatically reverted to OFF.
1
24 TORQUE CONTROL
Torque control variables
2401
TORQ RAMP UP
Defines the torque reference ramp up time, i.e the minimum time for the
reference to increase from zero to the nominal motor torque.
0
0.00…120.00 s
Time
1 = 0.01 s
2402
TORQ RAMP DOWN
Defines the torque reference ramp down time, i.e the minimum time for the
reference to decrease from the nominal motor torque to zero.
0
0.00…120.00 s
Time
1 = 0.01 s
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Speed reference
Actual speed
* No acceleration compensation
Acceleration compensation
t
t
%
%
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......