Actual signals and parameters
175
COMM
Fieldbus interface as the source for the inverted Start Enable (Start Disable)
signal, i.e. control word
FB CMD WORD 2 bit 18 (bit 19 for Start Enable
2). The control word is sent by the fieldbus controller via the fieldbus adapter
or embedded fieldbus (modbus) to the drive. For the control word bits, see
section
on page
.
Note:
This setting applies only for the DCU profile!
7
DI1(INV)
External signal required through inverted digital input DI1. 0 = Start Enable.
If Start Enable signal is switched off, the drive will not start or it coasts to stop
if it is running and alarm START ENABLE 1 MISSING is activated.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
1609
START ENABLE 2
Selects the source for the Start Enable 2 signal. See parameter
START
ENABLE 1.
NOT SEL
.
1610
DISPLAY ALARMS
Activates/deactivates alarms OVERCURRENT (2001), OVERVOLTAGE
(2002), UNDERVOLTAGE (2003) and DEVICE OVERTEMP (2009). For
more information see chapter
.
NO
NO
Alarms are inactive.
0
YES
Alarms are active.
1
1611
PARAMETER VIEW
Selects the parameter view, i.e which parameters are shown.
Note:
This parameter is visible only when it is activated by the optional
FlashDrop device. FlashDrop is designed for fast copying of parameters to
unpowered drives. It allows for easy customisation of the parameter list, e.g.
selected parameters can be hidden. For more information, see
MFDT-01
FlashDrop User’s Manual
[3AFE68591074 (English)].
FlashDrop parameter values are activated by setting parameter
APPLIC MACRO to LOAD FD SET.
DEFAULT
DEFAULT
Complete long and short parameter lists
0
FLASHDROP
FlashDrop parameter list. Does not include short parameter list. Parameters
which are hidden by the FlashDrop device are not visible.
1
18 FREQ IN & TRAN
OUT
Frequency input and transistor output signal processing.
1801
FREQ INPUT MIN
Defines the minimum input value when DI5 is used as a frequency input. See
section
on page
.
0
0…10000 Hz
Minimum frequency
1 = 1 Hz
1802
FREQ INPUT MAX
Defines the maximum input value when DI5 is used as a frequency input.
See section
on page
.
1000
0…10000 Hz
Maximum frequency
1 = 1 Hz
1803
FILTER FREQ IN
Defines the filter time constant for frequency input, i.e the time within 63% of
a step change is reached. See section
on page
.
0.1
0.0…10.0 s
Filter time constant
1 = 0.1 s
1804
TO MODE
Selects the operation mode for the transistor output TO. See section
on page
DIGITAL
DIGITAL
Transistor output is used as a digital output DO.
0
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......